Selection Guide
What should you look for when choosing a circulator pump?
The right circulator pump is not the most powerful model in the catalogue but the one that meets the system’s operating point with the least energy. Flow rate and head determine the choice; temperature, fluid, pressure rating and control mode narrow it down.
1. Calculate the required flow rate
The flow rate is found from the heat load to be transported and the difference between flow and return temperatures. For water, the practical formula is:
Here Q is the flow rate (m³/h), P the heat load (kW) and ΔT the temperature difference (K).
| Heat load | ΔT | Required flow rate |
|---|---|---|
| 24 kW | 20 K | approx. 1.0 m³/h |
| 100 kW | 20 K | approx. 4.3 m³/h |
| 100 kW | 10 K | approx. 8.6 m³/h |
The table shows an important point: for the same heat load, halving ΔT doubles the flow rate. That is why pump selection needs an extra check in low-temperature systems and with heat pumps.
2. Find the head from the losses, not the building height
In a closed circuit, head does not mean building height. What counts is the total pressure loss in the critical circuit with the highest resistance.
This total includes:
- Straight pipe and fittings
- Boiler, heat exchanger and manifold
- Valves, balancing valves and strainers
- Radiator, fan coil or underfloor heating circuit
Saying “make it the same head as the old one” without doing the calculation is a common mistake. If the old pump was oversized, the same mistake is carried over to the new pump.
3. Read the operating point on the curve
The calculated flow rate and head are marked on the pump curve. This point must lie within the control range of the chosen model.
The head value in the pump name refers to zero flow. A model ending in “-60”, for example, will not deliver 6 metres at the required flow rate. Always decide by looking at the curve.
An oversized pump not only wastes energy but can also cause noise at thermostatic valves. KSB also points out this noise.
4. Check fluid and temperature limits
The Calio, Calio Pro and Calio Pro Plus series operate at fluid temperatures from -10 to +110 °C. Limits may differ for other series and drinking water models; check the documentation of the model you choose.
Three situations need attention:
- Glycol: as the fluid becomes more viscous, the pump’s operating data must be corrected. KSB’s Calio manual specifies water-glycol mixtures up to a 1:1 ratio. Details in our glycol article.
- Cooling circuits: if the fluid is colder than the ambient air, there is a risk of condensation in the motor and terminal box. Check the manufacturer’s chilled water conditions before choosing.
- High temperature: the higher the temperature, the higher the required minimum inlet pressure. Our cavitation article explains this.
5. Confirm the pressure rating and connection size
In a multi-storey building, a pump on the lowest floor carries most of the static pressure. The pump’s PN rating must therefore cover the system’s maximum operating pressure. The Calio Pro Plus series covers PN 6, PN 10 and PN 16.
When replacing an old pump, check three dimensions: overall length (e.g. 130 or 180 mm), connection type (threaded or flanged) and connection diameter. The pipe diameter should not be smaller than the pump’s port diameter.
6. Choose the control mode to suit the system
KSB’s Calio manual distinguishes the modes as follows:
| Installation | Suitable starting point |
|---|---|
| Two-pipe radiator system with thermostatic valves | Proportional pressure (Δp-v), with DynamicControl if possible |
| Underfloor heating | Constant pressure (Δp-c) |
| Solar thermal circuit | Constant pressure (Δp-c) |
| System curve unknown | Standard setting + DynamicControl |
| Building automation in control | External signal or Modbus |
For details and savings figures, see our article on control modes.
7. Consider energy efficiency and building automation
In the EU and Türkiye, the upper limit for standalone glandless circulators is EEI 0.23. The lower the value on the label, the more efficient the pump; our EEI article explains how this value is calculated.
If the building has automation, plan the signal infrastructure from the start. Modbus RTU is standard on Calio Pro Plus; additional modules connect it to other automation systems.
8. Is redundancy needed?
In buildings where downtime is costly, such as hospitals, hotels or data centres, consider a twin pump. KSB offers the Calio Z, Calio Pro Z and Calio Pro Plus Z models for this purpose. Calio Pro Plus Z can keep one pump on standby or run both pumps together at peak load.
How do the KSB series differ?
| Series | Main use | Connection and head |
|---|---|---|
| Calio SI | Homes and small commercial buildings | G 1, G 1½ and G 2 union; 5 to 9.5 m |
| Calio SI HP MINI | Tight installation spaces | G 1 and G 1½ union; 130 or 180 mm length |
| Calio SI HP | Medium-sized residential and commercial buildings | G 1½ and G 2 union; 8 m |
| Calio | Building heating and air conditioning | G 1½ union to DN 100 flange; up to 18 m |
| Calio Pro | Large buildings | G 1½ to DN 65; up to 24 m³/h and 12 m |
| Calio Pro Plus | Large projects and building automation | G 1½ to DN 100; up to 18 m |
| Calio Z, Calio Pro Z, Calio Pro Plus Z | Redundant systems | Twin pump |
| Calio Therm and Calio SI Therm | Domestic hot water recirculation | Design suitable for drinking water |
For current sizes and curves, use the KSBuilding Consult selection tool or contact us.
Example: a building with 100 kW of radiators
The following example is fictitious and illustrates the method.
- Flow rate: heat load 100 kW, flow/return temperature 70/50 °C. With a difference of 20 K, the required flow rate is approx. 4.3 m³/h.
- Head: assume the losses in the critical circuit are calculated at 4.5 metres. The operating point is 4.3 m³/h and 4.5 metres.
- Model: look for this point on the curve, not by the head in the name. The smallest suitable size that meets the point within its control range is the one to choose.
- Control: as it is a two-pipe system with thermostatic valves, proportional pressure or DynamicControl is suitable.
- Pressure: if the pump is in the basement and the building’s water column is 30 metres, the static pressure is about 3 bar. Even with the pump’s differential added it stays below the PN 6 limit, but the safety valve setting must also be checked.
- Inlet pressure: the model’s minimum inlet pressure for 70 °C is compared with the system’s actual pressure.
If the same building used 30% glycol, steps 1 and 2 would be repeated with the properties of the mixture. That is why a ready-made table such as “this pump for 100 kW” is not enough on its own.
When replacing an old pump
A replacement is a good opportunity to redo the calculation. After insulation work or a new boiler or valves, the building’s heat load may have fallen. In that case, buying a pump of the same size may be unnecessary.
Photograph the old pump’s nameplate, measure the overall length and note the recent energy consumption if available. Comparing the same data after installing the new pump shows the gain in concrete terms.
Quick checklist
- Flow rate calculated from heat load and ΔT.
- Head calculated from the losses in the critical circuit.
- Operating point checked on the curve.
- Fluid, temperature and minimum inlet pressure confirmed.
- PN, overall length and connection type match.
- Control mode and automation needs defined.
Frequently asked questions
Is it safe to choose a pump one size larger?
Usually not. Excess pressure can cause noise at valves and increases energy consumption. Variable speed reduces the difference but does not fully cancel a wrong choice.
Can you choose a pump by the number of floors?
Not in a closed circuit. The number of floors affects pipe length and static pressure, but the choice is based on the calculated losses.
What if I have no calculation?
The existing pump’s curve and the building’s heat load are a good start. Still, consult a building services engineer before making a change. If the system curve is unknown, DynamicControl can be used on a suitable pump.