Circulator pump

Calio Pro

A smart, simple solution for large buildings

High-efficiency circulator pump for heating, ventilation and air-conditioning systems in large buildings. With infinitely variable speed control, integrated DynamicControl software and fluid temperatures from -10 °C to +110 °C, it is ideal for replacing uncontrolled pumps. Threaded and flanged connections and the Calio Pro Z twin pump version cover a wide range of applications.

Connection
G 1½ to DN 65
Head
4 to 12 m
Available options
32
  • Twin pump option
View Models

Extra energy savings with DynamicControl

The integrated DynamicControl software saves around 40 per cent more energy than conventional proportional pressure control. It needs no additional sensors or actuators and prevents undersupply when system conditions change.

Why Calio Pro?

  1. 01

    Powerful Performance

    Meets the needs of large buildings with flow rates up to 24 m³/h and heads up to 12 m.

  2. 02

    Easy Operation

    Settings are made with the buttons on the control panel; the keypad can be locked against unauthorised changes.

  3. 03

    Twin Pump Operation

    Duty and standby operation with automatic changeover on fault and by timer; no extra software or hardware needed.

  4. 04

    Building Automation Connection

    A volt-free general fault signal is standard and can be passed to the building management system.

  5. 05

    Wide Temperature Range

    Operates in heating, ventilation and air-conditioning systems at fluid temperatures from -10 °C to +110 °C.

  6. 06

    Union and Flange

    G 1½ and G 2 union and DN 32 to DN 65 flange connection options.

Calio Pro technical data

Casing material
Grey cast iron with cathodic electrocoating (EN‑GJL‑200)
Operating modes
Constant pressure (p-c), variable pressure (p-v), dynamic control, 3-step flow control
External control
None
Display
with display
Pressure rating
PN 6, PN 10, PN 16
Temperature class
TF 110
Energy efficiency (EEI)
≤ 0.20 to ≤ 0.21

Pump characteristic curves

The curves are taken from the type series booklet. Each chart shows the head (H) at the top and the power input (P1) at the bottom, with the flow rate (Q) on the horizontal axis. Select a model to see its curves, technical data and dimensions.

G 1½
G 2
DN 32
DN 40
DN 50
DN 65

Technical details

Operating data
PropertyCalio ProCalio Pro Z
Flow rateUp to 24 m³/hUp to 22 m³/h
HeadUp to 12 mUp to 12 m
Fluid temperature-10 to +110 °C-10 to +110 °C
Ambient temperature0 to +40 °C (max. +30 °C if the fluid is above 90 °C)0 to +40 °C (max. +30 °C if the fluid is above 90 °C)
Operating pressureUp to 16 barUp to 16 bar
Pressure ratingPN 6/10/16PN 6/10/16
Sound pressure levelBelow 40 dB(A)Below 40 dB(A)
Threaded connectionG 1½ and G 2G 2
Flanged connectionDN 32 to DN 65DN 32 to DN 50
Technical data

All models run on 1~230 V AC, 50/60 Hz. On threaded models the pipe is connected with pipe unions available as accessories.

Calio Pro

ModelPump connectionPipe connectionPNSpeed (rpm)Power input P1 (W)Current (A)Weight (kg)Material no.
25-40G 1½R ¾, R 16/10/161000 - 32007 - 800.15 - 0.805.3829135107
25-60G 1½R ¾, R 16/10/161000 - 37007 - 1250.15 - 1.005.3829135108
25-80G 1½R ¾, R 16/10/161000 - 42007 - 1650.15 - 1.005.3829135116
25-100G 1½R ¾, R 16/10/161000 - 47007 - 1850.15 - 1.055.6829135117
30-40G 2R 1¼6/10/161000 - 31007 - 700.15 - 0.705.5829135109
30-60G 2R 1¼6/10/161000 - 37007 - 1200.15 - 1.005.5829135110
30-80G 2R 1¼6/10/161000 - 42007 - 1600.15 - 1.055.5829135118
30-100G 2R 1¼6/10/161000 - 46007 - 1850.15 - 1.055.8829135119
30-120G 2R 1¼6/10/161000 - 41008 - 3400.15 - 1.506.5229135125
32-40DN 32DN 326/10/161000 - 31007 - 700.15 - 0.708.7429135111
32-60DN 32DN 326/10/161000 - 37007 - 1100.15 - 1.008.7429135112
32-80DN 32DN 326/10/161000 - 41007 - 1550.15 - 1.058.7429135120
32-100DN 32DN 326/10/161000 - 46007 - 1800.15 - 1.059.0429135121
32-120DN 32DN 326/10/161000 - 40008 - 3100.15 - 1.409.6829135126
40-40DN 40DN 406/10/161000 - 33007 - 950.15 - 0.908.7629135113
40-60DN 40DN 406/10/161000 - 38007 - 1100.15 - 1.058.7629135114
40-70DN 40DN 406/10/161000 - 41007 - 1350.15 - 1.058.7629135122
40-80DN 40DN 406/10/161000 - 37008 - 2900.15 - 1.4011.5529135127
40-90DN 40DN 406/10/161000 - 47007 - 1950.15 - 1.059.0629135123
40-100DN 40DN 406/10/161000 - 41008 - 3900.15 - 1.8511.5529135128
50-40DN 50DN 506/10/161000 - 33007 - 1300.15 - 1.059.9829135115
50-60DN 50DN 506/10/161000 - 34008 - 2700.15 - 1.2512.9329135129
50-80DN 50DN 506/10/161000 - 38008 - 3300.15 - 1.5012.9329135130
50-90DN 50DN 506/10/161000 - 48007 - 1750.15 - 1.0510.2829135124
65-60DN 65DN 656/10/161000 - 32008 - 3700.15 - 1.8017.6229135131

Calio Pro Z

ModelPump connectionPipe connectionPNSpeed (rpm)Power input P1 (W)Current (A)Weight (kg)Material no.
30-60G 2R 1¼6/10/161000 - 37007 - 1400.15 - 1.0513.6129135132
30-100G 2R 1¼6/10/161000 - 46007 - 1900.15 - 1.0514.229135133
32-80DN 32DN 326/10/161000 - 42007 - 1600.15 - 1.0517.9629135134
32-120DN 32DN 326/10/161000 - 40008 - 3600.15 - 1.6019.8429135135
40-80DN 40DN 406/10/161000 - 35008 - 3050.15 - 1.4021.229135136
40-100DN 40DN 406/10/161000 - 40008 - 4200.15 - 2.0021.229135137
50-80DN 50DN 506/10/161000 - 38008 - 4150.15 - 1.9527.3429135138
Motor and design
  • Maintenance-free, glandless high-efficiency wet rotor pump
  • Brushless, self-cooling permanent magnet synchronous motor with continuously variable differential pressure control
  • 1~230 V AC (±10%), 50/60 Hz
  • Enclosure IPX4D, thermal class F, temperature class TF 110
  • Product-lubricated special plain bearing, integrated motor protection
  • Energy efficiency index EEI ≤ 0.20 (Calio Pro Z 30-100: 0.21). The benchmark for the most efficient circulators is EEI ≤ 0.20.
  • Electromagnetic compatibility: EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3
Operating modes and functions

Operating modes

  • Constant pressure control (Δp-c)
  • Proportional pressure control (Δp-v)
  • Dynamic Control
  • Constant speed with 3 speed levels (open-loop control)

Automatic functions

  • Continuously variable speed adjustment according to the operating mode
  • Twin pump operation
  • Deblocking, self-venting of the pump casing, soft start
  • Full motor protection with integrated trip electronics

Manual settings

  • Operating mode
  • Head setpoint
  • Speed level
  • Rotor chamber venting
  • Keypad lock

Display and signals

  • Pump status (running or stopped)
  • Set head and speed level
  • Error code on the display
  • General fault message (volt-free contact)
Dynamic Control

Dynamic Control detects when the selected control curve is higher than the building needs and shifts it down automatically, reducing power consumption. When the minimum curve that still ensures adequate supply is reached, the pump switches back to a higher curve. The pump therefore runs at the best point even when the system curve is unknown, flow noise at thermostatic valves is reduced and up to 40% additional energy is saved compared with proportional pressure control.

Applications and fluids

Applications

  • Heating, ventilation, air-conditioning, cooling and circulation systems
  • One-pipe and two-pipe systems
  • Underfloor heating
  • Boiler and primary circuits
  • Storage tank charging circuits
  • Solar thermal systems and heat pumps

Suitable fluids

  • Heating water to VDI 2035
  • Higher-viscosity fluids: water and glycol mixture up to a ratio of 1:1
Materials
PartMaterial
Volute casing (102)Grey cast iron with cathodic electrocoating (EN-GJL-200)
Shaft (210)Stainless steel 1.4034
Impeller (230)Glass fibre reinforced plastic
Bearing (310)Ceramic / carbon
Thermal insulation shell (689)Polypropylene
Can (817)Glass fibre reinforced plastic (PSU-GF30 up to P1 400 W, PPS-GF40 above)

Casing parts in contact with the fluid and the atmosphere are free from paint-wetting impairment substances.

Minimum inlet pressure and temperature limits

Minimum pressure required at the pump inlet to avoid cavitation noise. The values apply up to 300 m above sea level; above that, add 0.01 bar per 100 m.

Fluid temperatureMinimum inlet pressure
Up to 80 °C0.5 bar
81 to 95 °C1.5 bar
96 to 110 °C2.5 bar
LimitValue
Fluid temperature-10 to +110 °C
Ambient temperature0 to +40 °C (max. +30 °C if the fluid is above 90 °C)
Dimensions and installation

All dimensions in mm. The letters refer to the dimensions in the drawing.

Calio Pro

Threaded model
Threaded model
Flanged model
Flanged model
ModelABCDEFHIJ
25-402095698180205196143108175
25-602095698180205196143108175
25-802095698180205196143108175
25-1002095698180205196143108175
30-402095698180205196143108175
30-602095698180205196143108175
30-802095698180205196143108175
30-1002095698180205196143108175
30-1202095698180205196143108175
32-4020965110220213196143108175
32-6020965110220213196143108175
32-8020965110220213196143108175
32-10020965110220213196143108175
32-12020965110220213196143108175
40-4021770120220218196143108175
40-6021770120220218196143108175
40-7021770120220218196143108175
40-8021770120220218196143108175
40-9021770120220218196143108175
40-10021770120220218196143108175
50-4021476120240226196143108175
50-6021476120240226196143108175
50-8021476120240226196143108175
50-9021476120240226196143108175
65-6022186170340236196143108175

Calio Pro Z

Threaded model
Threaded model
Flanged model
Flanged model
ModelABCDEFHIJ
30-602095182180470446268108175
30-1002095182180470446268108175
32-8020970110220470446268108175
32-12020970110220470446268108175
40-8021675121220470446268108175
40-10021675121220470446268108175
50-8022185126240470446268108175

Flange dimensions (mm)

Flange dimension drawing
FlangePN 6: Ø DPN 6: Ø kPN 6: holesPN 10/16: Ø DPN 10/16: Ø kPN 10/16: holes
DN 32120904 × Ø 141401004 × Ø 19
DN 401301004 × Ø 141501104 × Ø 19
DN 501401104 × Ø 141651254 × Ø 19
DN 651601304 × Ø 141851454 × Ø 19
DN 801901504 × Ø 192001608 × Ø 19
DN 1002101704 × Ø 192201808 × Ø 19

Permitted installation positions

Permitted installation positions for Calio Pro
Permitted installation positions for Calio Pro
Permitted installation positions for Calio Pro Z
Permitted installation positions for Calio Pro Z

Scope of supply

  • Pump
  • Two-part thermal insulation shell (Calio Pro)
  • Gaskets and washers
  • Electrical connector
  • Pre-configured twin pump connection cable and vent plug (Calio Pro Z)
  • Installation and operating manual
Accessories

Pipe unions

AccessoryConnectionMaterial no.
Pipe unions, set of 2 (G 1½ union nut, insert with Rp ¾ internal thread, steel)G 1½ / Rp ¾19075560
Pipe unions, set of 2 (G 1½ union nut, insert with Rp 1 internal thread, steel)G 1½ / Rp 119075561
Pipe unions, set of 2 (G 2 union nut, insert with Rp 1¼ internal thread, steel)G 2 / Rp 1¼19075562

Spacers (flanged models)

When replacing an old pump with a different installation length, spacers bridge the gap without modifying the pipework. All are rated PN 6/10/16.

SpacerFlangeLengthMaterial no.
F16DN 4030 mm19075991
F0DN 4070 mm19075566
F1DN 5010 mm19075567
F2DN 5020 mm19075568
F3DN 5050 mm19075569
F4DN 5060 mm19075570
F5DN 6510 mm19075571
F6DN 6525 mm19075572
F7DN 6530 mm19075573
F8DN 8010 mm19075574
F9DN 8015 mm19075575
F10DN 8020 mm19075576
F11DN 8025 mm19075577
F12DN 8030 mm19075578
F13DN 8040 mm19075579
F14DN 8050 mm19075580
F15DN 8080 mm19075581

Source: KSB type series booklets Calio Pro (1157.520/04, 15.12.2025) and Calio Pro Z (1157.530/05, 17.12.2025). The scope of supply may vary by model.

Calio Pro models

32 available options, 2 variants

Variant
Connection

How to read the model name

  • 25Connection: G 1½ union
  • 40Head: 4 m
ModelVariantConnectionHeadFlow rateMotor powerControlMaterial no.Quote
25-40 Standard G 1½ union 4 m 7 m³/h 80 W None 29135107
25-60 Standard G 1½ union 6 m 9 m³/h 125 W None 29135108
25-80 Standard G 1½ union 8 m 10 m³/h 165 W None 29135116
25-100 Standard G 1½ union 10 m 10.5 m³/h 185 W None 29135117
30-40 Standard G 2 union 4 m 7 m³/h 70 W None 29135109
30-60 Standard G 2 union 6 m 9 m³/h 120 W None 29135110
30-80 Standard G 2 union 8 m 10 m³/h 160 W None 29135118
30-100 Standard G 2 union 10 m 10.5 m³/h 185 W None 29135119
30-120 Standard G 2 union 12 m 14.5 m³/h 340 W None 29135125
32-40 Standard DN 32 flange 4 m 7 m³/h 70 W None 29135111
32-60 Standard DN 32 flange 6 m 9 m³/h 110 W None 29135112
32-80 Standard DN 32 flange 8 m 10 m³/h 155 W None 29135120
32-100 Standard DN 32 flange 10 m 10.5 m³/h 180 W None 29135121
32-120 Standard DN 32 flange 12 m 14.5 m³/h 310 W None 29135126
40-40 Standard DN 40 flange 4 m 10 m³/h 95 W None 29135113
40-60 Standard DN 40 flange 6 m 9 m³/h 110 W None 29135114
40-70 Standard DN 40 flange 7 m 10 m³/h 135 W None 29135122
40-80 Standard DN 40 flange 8 m 17 m³/h 290 W None 29135127
40-90 Standard DN 40 flange 9 m 10 m³/h 195 W None 29135123
40-100 Standard DN 40 flange 10 m 19 m³/h 390 W None 29135128
50-40 Standard DN 50 flange 4 m 10 m³/h 130 W None 29135115
50-60 Standard DN 50 flange 6 m 19.5 m³/h 270 W None 29135129
50-80 Standard DN 50 flange 8 m 22 m³/h 330 W None 29135130
50-90 Standard DN 50 flange 9 m 10 m³/h 175 W None 29135124
65-60 Standard DN 65 flange 6 m 24.5 m³/h 370 W None 29135131
30-60 Z (Twin) G 2 union 6 m 9 m³/h 140 W None 29135132
30-100 Z (Twin) G 2 union 10 m 10 m³/h 190 W None 29135133
32-80 Z (Twin) DN 32 flange 8 m 9.5 m³/h 160 W None 29135134
32-120 Z (Twin) DN 32 flange 12 m 14 m³/h 360 W None 29135135
40-80 Z (Twin) DN 40 flange 8 m 17.5 m³/h 305 W None 29135136
40-100 Z (Twin) DN 40 flange 10 m 20 m³/h 420 W None 29135137
50-80 Z (Twin) DN 50 flange 8 m 23 m³/h 415 W None 29135138

32 options shown

Z (twin) models: redundant operation or high flow option.

Product documents

Calio Pro

Single pump models

Installation and Operating ManualComing soon Type Series BookletComing soon

Calio Pro Z

Twin pump models

Installation and Operating ManualComing soon Type Series BookletPDF · 18 pages · 3.8 MB

Let’s choose the right Calio Pro model together.

Request a Quote

Fill in the form and our sales team will get back to you shortly.