Why does water boil below 100 °C?

Water does not only boil at 100 °C. The boiling point depends on pressure. The lower the pressure, the lower the temperature at which water vaporises.

As the flow enters the impeller it accelerates, and the pressure drops to its lowest value in a small zone. According to KSB’s lexicon, this drop is greatest at the blade inlet. If the pressure there falls below the vapour pressure of the water, bubbles form.

The risk grows with temperature because the vapour pressure rises quickly:

Water temperatureApprox. vapour pressure (absolute)
20 °C0.02 bar
80 °C0.47 bar
95 °C0.85 bar
110 °C1.43 bar

This table shows that water at 110 °C would already boil at atmospheric pressure. That is why high-temperature circuits need significant static pressure.

How does the damage occur?

When the bubbles are carried into a zone of higher pressure, they implode very rapidly. If the collapse happens close to a surface, a high-speed micro-jet of water forms and strikes the surface.

These repeated impacts erode the surface. If the protective layer is damaged, corrosion can accelerate too. KSB notes that material damage may not occur in every case of cavitating operation, but noise, rough running and a loss of efficiency appear earlier.

Is every bubble cavitation?

No, there are two different situations here. KSB distinguishes them as vapour and gas cavitation.

Vapour cavitationGas cavitation and air
Source of the bubbleWater vaporisingGas dissolved in the water or air in the system
Condition for formationPressure falls below vapour pressureCan form even at higher pressures
CollapseSudden implosionSlower dissolution
Effect on materialMore destructiveLess destructive, but reduces performance

In practice, air in the system can make a similar noise. So “the pump is noisy” does not always mean cavitation.

What does NPSH mean?

Cavitation is usually assessed with NPSH, which stands for net positive suction head.

  • NPSHA: the margin the system provides at the pump inlet, determined by system pressure, static height, losses and vapour pressure.
  • NPSHR: the margin the pump needs, determined by the manufacturer through testing.

The rule is simple: the value the system provides must be greater than what the pump requires. One detail matters, though. As KSB points out, NPSHR is often taken as NPSH3, the point at which cavitation reduces the head by 3%. So by the time this value is reached, cavitation has already begun; a safety margin is needed.

What it means in practice for circulators: minimum inlet pressure

Documentation for building services circulators usually gives a temperature-dependent minimum inlet pressure. On site, this value is much easier to use than an NPSH calculation.

The table below is an example from a KSB booklet showing how the values change with temperature.

Example (KSB Calio S, 2015)Fluid temperatureMinimum pressure at pump suction
Calio S5-75 °C0.05 bar
Calio S76-95 °C0.28 bar

According to KSB’s booklet, these values apply up to 300 metres. Above that, add 0.01 bar for every 100 metres. For a Calio S running with 90 °C water in a city 900 metres above sea level, for example: 0.28 + 0.06 = 0.34 bar.

The values vary by series. For the current table for the series we offer, see the product manual or ask us.

Causes and order of checks

Symptom or situationPossible causeWhat to check
Noise only increases when hotVapour pressure is risingMeasure the inlet pressure when hot
Pressure gauge lower than expectedLow water or a leakFill pressure and leaks
Pressure fluctuatesExpansion vessel problemPre-charge pressure and membrane
Pump at the highest pointLow static pressurePosition and minimum pressure
Valve or strainer on the suction sidePressure loss at the inletStrainer and valve position
Noise even before warming upAirVenting the pump and lines

KSB’s manual also states clearly that the flow must not be throttled on the suction side, to prevent cavitation damage. If the flow has to be throttled, the valve must be on the discharge side.

How can cavitation be prevented?

  1. Bring the system pressure to the design value and check it when hot.
  2. Check the expansion vessel’s pre-charge pressure and connection point. The pump’s position is decisive here.
  3. Lower the temperature if possible. A lower temperature both increases the cavitation margin and reduces heat losses.
  4. Remove any throttling and dirty strainers on the suction side.
  5. Complete the venting; in a complex system, consider an air separator.
  6. Confirm that the pump’s operating point is within the permitted range.

Especially with temperatures close to 100 °C, high altitude or a rooftop boiler room, consult an engineer before making changes.

On-site check: step by step

  1. Heat up the system. Take the measurement at normal operating temperature, not in a cold system.
  2. Read the inlet pressure. Use a pressure gauge close to the pump suction. If the gauge is at a different height, correct for the difference; 10 metres of water column is about 1 bar.
  3. Compare with the table value. Take the value for the actual temperature from the model’s documentation, plus any altitude allowance.
  4. Check the type of pressure in the document. Confirm from the manufacturer’s documentation whether the value is gauge or absolute pressure.
  5. Stop and start the pump. If the suction pressure drops noticeably when the pump runs, suspect that the pump is pumping towards the vessel.
  6. Find the cause. If the pressure is low, adding water is not enough. Also check for leaks and the condition of the expansion vessel.

Does glycol prevent cavitation?

Glycol lowers the freezing point but is not in itself a strong measure against cavitation. The boiling point of 30% by weight propylene glycol at atmospheric pressure, for example, is about 102 °C, not far from that of water. KSB also notes that converting NPSH values from one fluid to another largely requires testing. So the inlet pressure must be assessed separately in glycol circuits too.

Frequently asked questions

What does cavitation sound like?

It is usually described as sounding like gravel passing through the pump. Because air can make a similar sound, it is not a definite diagnosis on its own.

Can cavitation occur in a closed circuit?

Yes. Even though the pump does not work against the building height in a closed circuit, cavitation can occur if the inlet pressure is low and the water is hot.

Does cavitation damage the pump straight away?

Not always. It depends on severity and duration. But noise and loss of performance show that the problem needs fixing.

How can I detect cavitation without listening for it?

Measure the pump inlet pressure when hot and compare it with the manufacturer’s table. That is a more reliable first step than guessing.