Energy Efficiency
What is the energy efficiency index?
The energy efficiency index (EEI) is a number that compares the electricity a circulator pump draws in a standard usage scenario with a reference value. The lower the value, the less energy the pump needs for the same hydraulic work. For new standalone circulators, the upper limit is 0.23.
What does the label say?
On the pump nameplate the value usually appears as EEI ≤ 0.20. This means the index is not higher than the stated value.
| EEI | Meaning |
|---|---|
| 0.27 | The first EU limit for standalone circulators, introduced in 2013 |
| 0.23 | The EU limit in force since 1 August 2015 |
| 0.20 | The benchmark the regulation gives for the most efficient circulators |
0.20 is not a legal limit but a benchmark for comparison. The nameplate example in KSB’s Calio SI manual reads EEI ≤ 0.20.
Even within one series, the value can vary with size. In KSB’s 2019 Calio manual, the general value is EEI ≤ 0.20, while size 40-90 is given as 0.22 and size 50-90 as 0.21. So when deciding, look at the nameplate value of the size you choose.
What is the situation in Türkiye?
In Türkiye, the topic is governed by the Communiqué on Ecodesign Requirements for Glandless Standalone Circulators and Glandless Circulators Integrated in Products, which mirrors the EU regulation. Under the amendment of 31 December 2017:
- standalone glandless circulators from 1 February 2016,
- pumps integrated in products from 21 April 2018,
must not exceed an EEI of 0.23. The value also appears in public tenders: one of the Turkish ministry’s unit price definitions requires EEI ≤ 0.23 for wet rotor pumps.
How is the EEI calculated?
The calculation compares two powers: the pump’s weighted average power measured at four different flow rates and the reference power defined for a pump of the same size.
The pump is first measured at the point of maximum hydraulic power, which is taken as 100% flow. Electrical power is then measured at the four points below and weighted with the standard load profile.
| Flow rate | Share of time |
|---|---|
| %100 | %6 |
| %75 | %15 |
| %50 | %35 |
| %25 | %44 |
The table’s message is clear: a pump spends most of its time below full load. 79% of the time is spent at half the flow rate or less. That is why a pump that is not efficient at part load cannot achieve a good EEI.
The formula is:
Here P(L,avg) is the weighted average electrical power, P(ref) the reference power and P(hyd) the pump’s maximum hydraulic power. The factor 0.49 is a number that fixes the scale.
A simple example
Consider a fictitious pump with a hydraulic power of 100 W. Let the measured electrical power at 100%, 75%, 50% and 25% flow be 150, 110, 70 and 45 W respectively.
- Weighted average power: 0.06 × 150 + 0.15 × 110 + 0.35 × 70 + 0.44 × 45 = 69.8 W
- Reference power: 1.7 × 100 + 17 × (1 − e^−30) ≈ 187 W
- EEI: (69.8 / 187) × 0.49 ≈ 0.18
These figures only illustrate the method and do not belong to a real product. In a real calculation the measured head is also corrected. The detailed method is defined in the EN 16297 series of standards.
What the EEI does not tell you
The EEI is a very good tool for comparing two pumps by the same rules. But on its own it does not show your building’s energy bill.
- Wrong size: an oversized pump with a low EEI can consume more than a correctly sized pump.
- Control setting: the same pump wastes energy on a curve that is set too high.
- System balance: an unbalanced system can make the pump run at a higher pressure than necessary.
- Running time: the heating season and operating hours directly change consumption.
Between two pumps of similar size, however, the difference is meaningful. At the same reference power, an EEI falling from 0.23 to 0.20 means about 13% less weighted power in the standard profile. Note, though, that the “≤” sign on the nameplate means the real value may be even lower.
How to use the EEI when buying
Comparing EEI values makes sense when choosing between the right pumps.
- Determine the size first. Only compare pumps that meet the same operating point.
- Check the nameplate value. Look at the value for the size offered, not the general value for the series.
- Ask about the standard. Confirm that the value is given under EN 16297. KSB’s Calio SI manual cites EN 16297-3 for its value.
- Convert the difference into kilowatt hours. Work out whether a small EEI difference is worth the extra cost.
Here is a fictitious example. Compare a pump with EEI 0.23 and a weighted average power of 80 W with a pump of EEI 0.20 at the same reference power. The second pump’s weighted power is about 70 W. At 5,000 hours a year, consumption comes to 400 and 348 kWh, a difference of about 52 kWh.
For a single small pump this difference stays modest. It becomes more significant with large pumps or in buildings with many pumps. The right size and control setting, however, often make a bigger difference than the EEI gap between two new pumps.
A very old pump may have no EEI on its nameplate. In that case, compare using measured electrical power and running time rather than the EEI.
Which pumps are excluded?
The regulation covers glandless circulators with a hydraulic power of 1 to 2,500 W. According to the EU text, drinking water circulators are not subject to this limit apart from information requirements. Dry rotor pumps do not fall under the definition of “glandless” either.
So do not compare the EEI values of a domestic hot water recirculation pump and a heating pump with the same expectations.
Are new rules coming?
The European Commission launched a review of Regulation 641/2009 in 2025 and collected feedback until April 2025. The source does not say which requirements will change. For a new project, it is worth checking the current text.
Frequently asked questions
What should the EEI be?
A new standalone circulator needs 0.23 or lower. 0.20 and below is the benchmark level in the regulation.
Are the EEI and the energy class the same thing?
No. The old A to G labels used a different scale. Today, look at the EEI itself when deciding.
Does a low EEI always mean a low energy bill?
No. The EEI compares pumps under standard conditions. The bill depends on size, setting, the system and running time as well. Our article on control modes explains much of this difference.
Sources
- EU Regulation 622/2012
- KSB Calio SI manual
- KSB Calio manual (2019)
- Turkish Official Gazette: amendment to the circulator communiqué
- Turkish ministry unit price definition 25.350.3001
- REHVA: review of the EU circulator regulation
Example calculations and fictitious scenarios are marked as such in the text. This article is for general information only; for decisions specific to your project, consult a building services engineer.