What does glycol bring to the system?

1. Strong protection against corrosion. Steel radiators, cast iron casings and soldered joints in closed circuits corrode over time. Inhibited glycol almost stops this process. The annual corrosion rates measured in Dow’s ASTM D1384 laboratory test show the difference clearly:

MetalWaterUninhibited propylene glycolInhibited propylene glycol
Steel246 µm249 µm1 µm
Cast iron536 µm411 µm3.8 µm
Solder80 µm881 µm0.8 µm
Aluminium335 µm46 µmNo corrosion (slight weight gain)
Copper2 µm4 µm5 µm
Brass5.6 µm5.1 µm4.1 µm

The values are annual corrosion depths; results given in mils per year in the source have been converted to micrometres. Dow’s DOWFROST fluid was tested as the inhibited product. The results were measured under laboratory conditions for comparison. With the inhibited product, corrosion is about 250 times lower than with water on steel and about 140 times lower on cast iron. The table also shows an important point: the protection comes not from the glycol itself but from its inhibitors. Uninhibited glycol can cause even more corrosion than water, especially on solder. So always choose an inhibited product formulated for heat transfer.

2. Cleaner water, longer pump life. As steel and cast iron rust, fine iron oxide particles called magnetite get into the water. This black sludge is one of the biggest dangers for pumps. Many high-efficiency circulators, such as Calio Pro Plus, run on a permanent magnet synchronous motor. The magnetic rotor attracts the magnetite in the water. The particles build up, brake the rotor, jam the pump and reduce its efficiency.

The problem is not small. According to an article in the trade publication PHC News, about 70% of circulator pumps returned to manufacturers fail because of iron oxide damage. Pump manufacturer Xylem states that heavy magnetite build-up can cut system efficiency by 10% to 50% and recommends flushing the system, using inhibitors and fitting a magnetic filter as precautions.

Because inhibited glycol reduces corrosion at its source, it also reduces magnetite formation. The result is fewer pump failures, longer pump life and heat exchangers that do not clog.

3. Insurance against frost damage. A burst pipe or heat exchanger costs more than the part alone; water damage and heating downtime add to the bill. If frost protection on outdoor lines depends only on the pump running, a power cut leaves the system exposed. Glycol keeps protecting even when the power fails or the building stands empty.

4. Controlled, predictable operation. In glycol systems the fluid is measured regularly. This habit makes the system’s health visible: a drop in concentration reveals unnoticed leaks early.

Which systems should use it?

Since corrosion and sludge can form in any closed circuit, the protection of inhibited glycol benefits every heating and cooling system. Glycol is strongly recommended in these systems in particular:

  • Lines running outside the building or through unheated areas
  • Heat pump and chiller circuits with outdoor units
  • Solar collector and snow-melting circuits
  • Holiday homes and buildings left unused for long periods in winter
  • Systems that combine steel radiators, cast iron and other metals
  • Systems with high-efficiency circulators with magnet motors

In indoor systems with a low frost risk, a lower concentration is enough. Here the aim is corrosion protection rather than frost protection. Because Dow requires the inhibitor level to be adjusted separately in solutions below 20%, 20% can be taken as a practical lower limit.

What to allow for in the design

The physical properties of a glycol mixture differ slightly from water. If these differences are taken into account at the design stage, the system runs without problems:

PropertyDataWhat to do in the design
Heat transfer0.97 with 20% propylene glycol; 0.90 with 50% (82 °C, same flow rate, relative to water)Increase the flow rate slightly accordingly
Viscosity40% mixture: 1.18 at 65 °C; 7.2 at 10 °C; 48.9 mPa·s at −20 °CCalculate pressure loss for the mixture
Pump powerChanges in proportion to densityCheck motor load
ExpansionVessel 1.2 times larger than for a water system recommendedSize the expansion vessel accordingly

Correction values vary with product and temperature. The same manufacturer document, for example, gives a head correction for 50% ethylene glycol of 1.23 at 82 °C and 1.49 at 38 °C. So calculate with the mixture’s actual operating temperature.

How to choose the concentration

First define the protection you need. Dow’s table distinguishes two different needs:

  • Freeze protection: the fluid stays pumpable without forming ice crystals. This is needed if the system has to run in the cold.
  • Burst protection: the fluid may turn slushy but will not burst the pipe if there is expansion volume. This may be enough if the system will not start up in the cold.
Lowest temperatureFreeze protection (product by volume)Burst protection (product by volume)
−7 °C%19.1%12.8
−12 °C%30.9%21.3
−18 °C%38.3%25.5
−23 °C%44.7%29.8
−29 °C%48.9%31.9

The table is taken from the DOWFROST HD technical data sheet and gives typical values for that product only. Check the table for the product you use. Dow recommends designing for at least 3 °C below the lowest expected temperature.

A concentration much higher than needed is unnecessary; it puts needless strain on heat transfer and the pump. Boiler manufacturers often set 50%, and in some high-efficiency applications 35%, as the upper limit. For corrosion protection, as noted above, 20% is the practical lower limit.

What to check on the pump side

KSB’s 2019 Calio manual lists water-glycol mixtures up to a 1:1 ratio as permitted fluids. KSB’s other manuals also state that the operating data must be adapted to the higher viscosity depending on the glycol content.

Make four checks:

  1. Confirm the permitted glycol concentration in the current documentation for the chosen model.
  2. Calculate flow rate and head for the mixture, not for water.
  3. Check the maximum permitted viscosity in the model’s documentation. The value given for −20 °C in the table above may be far above what circulators accept.
  4. Check the pump’s minimum fluid temperature. For the Calio, Calio Pro and Calio Pro Plus series, the lower limit is −10 °C; it may differ for other models.

Keeping the protection effective for the long term

Inhibitors are used up over time; for the protection to last for years, regular checks are essential. Glycol life varies with product and conditions. According to one source, the design life is 3 to 5 years for economy products and up to 15 years for premium products. Another manufacturer speaks of lives of more than 20 years; a clean, well-maintained system extends this life.

Noble’s guide recommends the following monitoring:

  • First measurement: carry out a baseline analysis 2 to 4 weeks after filling.
  • Annual measurement: check concentration, pH and the general condition of the fluid at least once a year.
  • Refractometer: a steadily falling concentration may indicate a leak.
  • pH below 8.0: much of the inhibitor may be used up; ask the product manufacturer about topping it up.
  • pH below 7.0: the glycol may have oxidised; flush the system and replace the fluid.

These thresholds may vary by product. Go by the documentation for your own product.

The most common mistakes

  • Using automotive antifreeze. The silicates in these products can gel and reduce heat transfer.
  • Using uninhibited glycol. As the table above shows, the protection comes from the inhibitor.
  • Mixing with hard water. Noble recommends total hardness below 100 ppm and chloride and sulphate below 25 ppm. Pre-mixed products made with purified water reduce this risk.
  • Filling a dirty system. Glycol alone does not remove existing magnetite. Flush the system before filling and fit a magnetic filter if possible.
  • Leaving automatic water make-up on. Unnoticed dilution quietly reduces frost and corrosion protection.
  • Skipping the material compatibility check. Standard propylene glycol may not suit aluminium heat exchangers or galvanised pipe. Ask the boiler and heat exchanger manufacturer.
  • Trapping part of the circuit. A check valve or closed valve that fully isolates a section can prevent expansion and lead to frost damage.

If there is a domestic water or mains connection, also check local requirements. In some cases a backflow preventer or physical separation is needed.

Example decision: a system with an outdoor line

As a fictitious example, assume the lowest expected temperature is −15 °C. With the 3 °C margin Dow recommends, the −18 °C row of the table is chosen.

If the system has to keep running at this temperature, freeze protection needs about 38.3% product. If the system will not run in these conditions and only needs burst protection, the figure drops to about 25.5%. As both concentrations are above 20%, corrosion protection is also provided. A lower concentration means lower viscosity and better heat transfer for years, but requires operating rules such as not running the pump while the fluid is slushy.

Conclusion

Inhibited glycol is an investment that protects the system from frost and corrosion at the same time. Less corrosion also means less magnetite sludge, which means longer-lasting circulator pumps with fewer failures. With the right concentration, a suitable product and annual checks, this benefit lasts for the life of the system.

Frequently asked questions

Does glycol extend pump life?

Because inhibited glycol reduces corrosion, it also reduces magnetite sludge in the water. Magnetite is one of the most common causes of failure in high-efficiency circulators with magnet motors. Water that stays clean lets the pump run longer and without problems.

Does glycol reduce efficiency?

The mixture carries slightly less heat than water; with 20% propylene glycol, for example, the difference is about 3%. This is offset by choosing the right pump and setting the flow rate. In return, glycol prevents efficiency losses caused by corrosion and sludge.

Can glycol be added to an existing system?

Yes. First check the system volume, material compatibility, expansion vessel and pump. If the existing water is not clean, flush the system first.

Which glycol should be used?

In building services, inhibited propylene glycol formulated for heat transfer is preferred. Do not use automotive antifreeze or uninhibited glycol. Manufacturer documentation and local regulations should determine the final choice.

Sources

Example calculations and fictitious scenarios are marked as such in the text. This article is for general information only; for decisions specific to your project, consult a building services engineer.