Circulator pump
Calio Therm
Stainless steel pump for drinking water circulation
High-efficiency wet rotor circulator pump for drinking and domestic water systems. With its stainless steel casing, it is used in buildings that need hot water circulation, such as homes, hotels and hospitals. Infinitely variable differential pressure control and an integrated display show the operating status at all times.
- Connection
- G 1½, G 2 and DN 40
- Head
- 8 to 12 m
- Available options
- 5
- Suitable for drinking water
C23A_5076192267-1_0

From union to flange
Options range from G 1½ and G 2 threaded models to DN 40 flanged models, with heads from 8 to 12 m and flow rates up to 24 m³/h. The maintenance-free design runs trouble-free for many years.
Why Calio Therm?
-
01
Stainless Steel Casing
Stainless steel casing that resists the corrosive effects of drinking and domestic water.
-
02
Suitable for Drinking Water
Developed for drinking water and domestic hot water circulation systems.
-
03
Infinitely Variable Differential Pressure Control
Efficient, demand-driven operation with variable speed and infinitely variable differential pressure control.
-
04
Integrated Display
The operating status can be monitored at any time via the display and symbols.
-
05
Heads up to 12 m
Sufficient head for hot water circuits in large buildings.
-
06
Maintenance-Free
Maintenance-free, long-life operation thanks to the wet rotor design.
Calio Therm technical data
- Casing material
- Stainless steel 1.4308
- Operating modes
- Constant pressure (p-c), variable pressure (p-v), Eco mode, Boost mode
- External control
- 0-10 V, Modbus
- Display
- with display
- Pressure rating
- PN 6, PN 10
- Temperature class
- TF 110
Pump characteristic curves
The curves are taken from the type series booklet. Each chart shows the head (H) at the top and the power input (P1) at the bottom, with the flow rate (Q) on the horizontal axis. Select a model to see its curves, technical data and dimensions.
CalioTherm Pro 25-80
- Connection
- G 1½ union
- Speed
- 1000 - 4000 rpm
- Power input (P1)
- 3.5 - 180 W
- Current
- 0.15 - 0.86 A
- Pressure rating
- PN 6/10
- Weight
- 4.6 kg
- Material no.
- 29134853



CalioTherm Pro 25-80 dimensions
Threaded model. The letters refer to the dimensions in the drawing.
- A
- 197 mm
- B
- 53 mm
- C
- 98 mm
- D
- 180 mm
- E
- 137 mm
- F
- 168 mm
CalioTherm Pro 30-100
- Connection
- G 2 union
- Speed
- 1000 - 4500 rpm
- Power input (P1)
- 3.5 - 180 W
- Current
- 0.15 - 0.85 A
- Pressure rating
- PN 6/10
- Weight
- 4.8 kg
- Material no.
- 29134854



CalioTherm Pro 30-100 dimensions
Threaded model. The letters refer to the dimensions in the drawing.
- A
- 197 mm
- B
- 53 mm
- C
- 98 mm
- D
- 180 mm
- E
- 137 mm
- F
- 168 mm
CalioTherm Pro 30-120
- Connection
- G 2 union
- Speed
- 1000 - 4000 rpm
- Power input (P1)
- 3.5 - 330 W
- Current
- 0.15 - 1.50 A
- Pressure rating
- PN 6/10
- Weight
- 6.4 kg
- Material no.
- 29134855



CalioTherm Pro 30-120 dimensions
Threaded model. The letters refer to the dimensions in the drawing.
- A
- 232 mm
- B
- 53 mm
- C
- 98 mm
- D
- 180 mm
- E
- 137 mm
- F
- 168 mm
CalioTherm Pro 40-80
- Connection
- DN 40 flange
- Speed
- 1000 - 3600 rpm
- Power input (P1)
- 3.5 - 265 W
- Current
- 0.15 - 1.22 A
- Pressure rating
- PN 6/10
- Weight
- 11.1 kg
- Material no.
- 29134849



CalioTherm Pro 40-80 dimensions
Flanged model. The letters refer to the dimensions in the drawing.
- A
- 242 mm
- B
- 70 mm
- C
- 120 mm
- D
- 220 mm
- E
- 137 mm
- F
- 168 mm
CalioTherm Pro 40-100
- Connection
- DN 40 flange
- Speed
- 1000 - 4000 rpm
- Power input (P1)
- 3.5 - 360 W
- Current
- 0.15 - 1.65 A
- Pressure rating
- PN 6/10
- Weight
- 11.1 kg
- Material no.
- 29134856



CalioTherm Pro 40-100 dimensions
Flanged model. The letters refer to the dimensions in the drawing.
- A
- 242 mm
- B
- 70 mm
- C
- 120 mm
- D
- 220 mm
- E
- 137 mm
- F
- 168 mm
Technical details
Operating data
| Property | CalioTherm Pro |
|---|---|
| Flow rate | Up to 24 m³/h |
| Head | Up to 12 m |
| Fluid temperature | +2 to +70 °C (briefly up to +75 °C for max. 5 minutes) |
| Water hardness | Max. 20 °dH (35.7 °fH) |
| Ambient temperature | 0 to +40 °C |
| Operating pressure | Up to 10 bar |
| Pressure rating | PN 6/10 |
| Sound pressure level | Max. 40 dB(A) |
| Threaded connection | G 1½ and G 2 |
| Flanged connection | DN 40 |
To prevent limescale, limiting the fluid temperature to 65 °C is recommended. Brief higher temperatures, e.g. for thermal disinfection, are permitted.
Technical data
All models run on 1~230 V AC, 50/60 Hz. On threaded models the pipe is connected with pipe unions available as accessories.
| Model | Pump connection | Pipe connection | PN | Speed (rpm) | Power input P1 (W) | Current (A) | Weight (kg) | Material no. |
|---|---|---|---|---|---|---|---|---|
| 25-80 | G 1½ | R 1 | 6/10 | 1000 - 4000 | 3.5 - 180 | 0.15 - 0.86 | 4.6 | 29134853 |
| 30-100 | G 2 | R 1¼ | 6/10 | 1000 - 4500 | 3.5 - 180 | 0.15 - 0.85 | 4.8 | 29134854 |
| 30-120 | G 2 | R 1¼ | 6/10 | 1000 - 4000 | 3.5 - 330 | 0.15 - 1.50 | 6.4 | 29134855 |
| 40-80 | DN 40 | DN 40 | 6/10 | 1000 - 3600 | 3.5 - 265 | 0.15 - 1.22 | 11.1 | 29134849 |
| 40-100 | DN 40 | DN 40 | 6/10 | 1000 - 4000 | 3.5 - 360 | 0.15 - 1.65 | 11.1 | 29134856 |
Motor and design
- Maintenance-free, glandless high-efficiency wet rotor pump
- Brushless, self-cooling permanent magnet synchronous motor with continuously variable differential pressure control
- 1~230 V AC (±10%), 50/60 Hz
- Enclosure IPX4D, thermal class F, temperature class TF 110
- Product-lubricated special plain bearing, integrated motor protection
- Electromagnetic compatibility: EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3
- All wetted parts are approved for drinking water circulation systems; French drinking water approval (ACS)
Operating modes and functions
Operating modes
- Constant pressure control (Δp-c)
- Proportional pressure control (Δp-v)
- Eco-Mode
- Constant speed operation with a setpoint (open-loop control)
- Temperature-dependent differential pressure control (activated via KSB ServiceTool only)
Automatic functions
- Continuously variable speed adjustment according to the operating mode
- Dynamic Control
- External differential pressure setpoint or speed via 0-10 V signal
- 0-10 V input for actual temperature or differential pressure value
- Twin pump operation
- High flow demand mode
- Night setback
- Remote on/off
- Deblocking, self-venting of the pump casing, soft start
- Full motor protection with integrated trip electronics
Manual settings
- Operating mode
- Head setpoint
- Speed level
- Keypad lock
Display and signals
- The display alternates between flow rate, head and power input
- Operating status and error code on the display
- Configurable general fault and run signal (volt-free contact)
- Modbus RTU serial digital interface
- Service interface for KSB ServiceTool
Eco-Mode and Dynamic Control
Eco-Mode
In Eco-Mode the pump follows a quadratic curve: starting from the set head (HS), the curve drops to a quarter of that value at zero flow (H0 = 1/4 × HS). Power consumption is about 40% lower than with proportional pressure control. Changing the setpoint adapts the curve to a higher or lower pressure.
Dynamic Control
Dynamic Control detects when the selected control curve is higher than the building needs and shifts it down automatically, reducing power consumption. When the minimum curve that still ensures adequate supply is reached, the pump switches back to a higher curve. The pump therefore runs at the best point even when the system curve is unknown, flow noise at thermostatic valves is reduced and up to 40% additional energy is saved compared with proportional pressure control.
Applications and fluids
Applications
- Drinking water circulation systems to DVGW W 551
Suitable fluids
- Drinking water (TrinkwV 2001)
Materials
| Part | Material |
|---|---|
| Volute casing (102) | Stainless steel 1.4308 |
| Shaft (210) | Stainless steel 1.4034 |
| Impeller (230) | Glass fibre reinforced plastic (PSU-GF30) |
| Bearing (310) | Ceramic / carbon |
| Thermal insulation shell (689) | Polypropylene |
| Can (817) | Glass fibre reinforced plastic (PPS-GF40) |
Casing parts in contact with the fluid and the atmosphere are free from paint-wetting impairment substances.
Minimum inlet pressure and temperature limits
Minimum pressure required at the pump inlet to avoid cavitation noise. The values apply up to 300 m above sea level; above that, add 0.01 bar per 100 m.
| Fluid temperature | Minimum inlet pressure |
|---|---|
| Up to 70 °C | 0.5 bar |
| Limit | Value |
|---|---|
| Fluid temperature | +2 to +70 °C |
| Ambient temperature | 0 to +40 °C |
Modbus interface
The pump connects to the building automation system via its Modbus RTU interface.
| Property | Value |
|---|---|
| Interface | RS485 (TIA-485A), optically isolated |
| Protocol | Modbus RTU |
| Baud rate | 4,800, 9,600, 19,200 (factory setting), 38,400, 57,600, 115,200 baud |
| Data format | 8 data bits, parity EVEN, ODD or NONE, 1 stop bit |
| Modbus address | Selectable from 1 to 247 (factory setting 17) |
| Cable | Twisted-pair bus cable, 0.5 mm²; terminal cross-section 1.5 mm² |
| Line length | Max. 1000 m; provide surge protection for lines longer than 30 m |
| Line termination | 120 Ω (TIA-485-A, line type B) |
Dimensions and installation
All dimensions in mm. The letters refer to the dimensions in the drawing.


| Model | A | B | C | D | E | F |
|---|---|---|---|---|---|---|
| 25-80 | 197 | 53 | 98 | 180 | 137 | 168 |
| 30-100 | 197 | 53 | 98 | 180 | 137 | 168 |
| 30-120 | 232 | 53 | 98 | 180 | 137 | 168 |
| 40-80 | 242 | 70 | 120 | 220 | 137 | 168 |
| 40-100 | 242 | 70 | 120 | 220 | 137 | 168 |
Flange dimensions (mm)

| Flange | PN 6: Ø D | PN 6: Ø k | PN 6: holes | PN 10: Ø D | PN 10: Ø k | PN 10: holes |
|---|---|---|---|---|---|---|
| DN 40 | 130 | 100 | 4 × Ø 14 | 150 | 110 | 4 × Ø 19 |
Permitted installation positions

Scope of supply
- Pump
- Two-part thermal insulation shell
- Flat gaskets and washers
- Installation and operating manual
Accessories
Pipe unions
| Accessory | Connection | Material no. |
|---|---|---|
| Pipe unions, set of 2 (G 1½ union nut, insert with Rp 1 internal thread, brass) | G 1½ / Rp 1 | 19075564 |
| Pipe unions, set of 2 (G 2 union nut, insert with Rp 1¼ internal thread, brass) | G 2 / Rp 1¼ | 19075565 |
Source: KSB type series booklet CalioTherm Pro (1157.581/09, 17.07.2026). Also applies to Calio-Therm. The scope of supply may vary by model.
Calio Therm models
5 available options
How to read the model name
- 25Connection: G 1½ union
- 80Head: 8 m
| Model | Connection | Head | Flow rate | Motor power | Control | Material no. | Quote |
|---|---|---|---|---|---|---|---|
| 25-80 | G 1½ union | 8 m | 11 m³/h | 180 W | 0-10 V, Modbus | 29134853 | |
| 30-100 | G 2 union | 10 m | 12 m³/h | 180 W | 0-10 V, Modbus | 29134854 | |
| 30-120 | G 2 union | 12 m | 15.5 m³/h | 330 W | 0-10 V, Modbus | 29134855 | |
| 40-80 | DN 40 flange | 8 m | 21 m³/h | 265 W | 0-10 V, Modbus | 29134849 | |
| 40-100 | DN 40 flange | 10 m | 24 m³/h | 360 W | 0-10 V, Modbus | 29134856 |
No model matches this selection.
5 options shown
Product documents

CalioTherm Pro
Also applies to Calio Therm