What do control modes do?

The pump adjusts its speed according to a control curve. The difference between the modes is how much pressure the pump keeps up as the flow rate falls.

ModeWhen flow fallsSuitable use
Constant speedSpeed stays the sameSpecial cases where automatic control is not wanted
Constant pressure (Δp-c)Pressure stays the sameUnderfloor heating and solar circuits
Proportional pressure (Δp-v)Pressure fallsRadiator heating systems
Eco ModePressure falls further along a parabolic curveAlternative to proportional pressure
DynamicControlLowers the operating point to match demandSystems with an unknown system curve

The manual also recommends switching from constant to proportional pressure if noise is heard at low flow.

Why is energy still wasted?

A variable speed pump can also be set to a curve that is higher than necessary. KSB explains this problem with the minimum system curve, which shows the system’s friction losses with all thermostatic valves fully open.

The designer or installer often does not know this curve, so to be on the safe side they choose a higher curve. The difference between the selected curve and the minimum system curve is wasted energy. A setting that is too high can also cause noise at thermostatic valves.

How does DynamicControl work?

DynamicControl lowers the operating point from the selected curve towards the minimum system curve. If undersupply is detected, the pump returns immediately to the original curve.

According to KSB, the function is software-based. It needs no additional sensors or actuators; the pump takes the information it needs from its own internal signals. It is available in the Calio, Calio Pro and Calio Pro Plus series and can be added to third-generation Calio pumps with a software update.

Use may vary by model. While KSB’s article says no extra setting is needed, the 2019 Calio manual refers to activating the function and adjusting it with the ServiceTool. Check the pump’s own manual.

What are the figures compared with?

When comparing savings percentages, the question “compared with what?” matters as much as the percentage itself. KSB sources contain different comparisons.

FunctionBaselineStated savingsSource
DynamicControlConventionally controlled pumpup to 20%; average 20% in steady operationKSB magazine
Eco ModeProportional pressureup to 53%, average 36% (example for size 25-100)Calio manual
Eco ModeProportional pressureadditional savings of more than 40%Calio S BMS booklet, 2015
DynamicControlConventional proportional pressureapprox. 40%Calio Pro press release

These values are the manufacturer’s data and are not guaranteed for every system. In marketing copy, writing “up to 40% compared with proportional pressure control” instead of “40% savings” is both more accurate and more trustworthy.

What does this mean in kilowatt hours?

The calculation is simple: average power × operating hours × savings rate. Use the pump’s actual average power here, not the rated power on the label.

The following example is fictitious: a pump drawing an average of 400 W runs for 5,000 hours a year.

ScenarioAnnual consumption or savings
Current consumption2,000 kWh
20% savings400 kWh
40% savings800 kWh

Multiply these savings by your electricity unit price to find the monetary value. In a single boiler room the amount may look small, but in buildings with several pumps and a long heating season the difference grows.

What determines the savings?

  • System balance: an unbalanced system forces the pump to run at high pressure. Correct the hydraulic balance first.
  • Initial setting: the gain is greater with a pump set too high. With a correctly set pump, the difference is smaller.
  • Part-load time: the gain is greater in variable-flow systems with thermostatic valves.
  • Size: an oversized pump can be partly compensated by the control mode, but the problem does not go away.
  • System type: in circuits where thermostatic valves do not change the system curve, such as solar pumps, proportional control is not needed. Do not expect a similar gain in such circuits.

Is there a risk of insufficient heating?

The manual gives a clear warning: with proportional pressure, a curve set too low causes undersupply, and one set too high increases energy use. In Eco Mode too, the chosen setting must meet the system curve.

For DynamicControl, KSB states that the patented technology practically prevents undersupply. Even so, after adjusting the settings, check that the most distant radiators heat up and that there is no valve noise.

How can you measure the savings in your building?

  1. Record consumption before changing the pump or setting. If there is no energy meter, read the power on the pump display regularly.
  2. Compare periods with similar heating conditions. If the weather is milder, the pump runs less anyway.
  3. Make one change at a time. If valve balancing or boiler settings change at the same time, you cannot tell where the difference comes from.
  4. Monitor comfort as well as energy. Temperatures in distant flats or rooms should not drop.

The energy meter found on some models such as Calio Pro Plus makes this measurement easier.

Which mode should I choose?

The following sequence is based on the recommendations in KSB’s Calio manual.

  1. Identify the system type. Constant pressure is the starting point for underfloor heating and solar circuits, proportional pressure for radiator systems.
  2. Is the system curve known? If hydraulic balancing has been done, choose the control curve just above the system curve.
  3. If not, use DynamicControl. In this case the manual recommends activating the function together with the standard setting. Activating it is also recommended if the curve is known.
  4. Consider Eco Mode. The manual prefers Eco Mode to proportional pressure control. At zero flow, the set pressure is 50% lower than with proportional control.
  5. Test on a cold day. The lowest setting must also be sufficient at peak heat demand. Check distant radiators and the return temperature.
  6. Consider night mode. According to the manual, the night setback function reduces flow rate, noise and power consumption. Make sure it does not conflict with the heating control.

If the building automation sends the pump an external speed command, the savings depend on that control logic. In this case do not expect the catalogue figures directly; assess the automation scenario separately.

Frequently asked questions

What is the difference between Δp-c and Δp-v?

Δp-c keeps the pressure the same even when the flow changes. Δp-v lowers the pressure as the flow falls. Δp-v is usually preferred in radiator systems with thermostatic valves.

Can I update my existing Calio pump?

KSB states that DynamicControl can be added to third-generation Calio pumps with a software update. For your model, ask an authorized service partner or dealer.

Is this saving reflected in the boiler fuel bill?

Not as a direct percentage. These figures refer to the pump’s electricity. Reducing unnecessarily high pressure can improve valve noise and control, but do not expect the same percentage for boiler fuel.

Sources

Example calculations and fictitious scenarios are marked as such in the text. This article is for general information only; for decisions specific to your project, consult a building services engineer.