Selection Guide
Circulator pump or booster pump? Choosing the right pump for domestic hot water and solar systems
When looking for a pump for comfortable hot water or a solar system, needs that look similar at first glance may call for different solutions. The first step in choosing the right pump is to determine whether the water is to be circulated in a closed circuit or delivered under pressure to the point of use.
In this article you will find the key difference between a circulator pump and a booster pump, which applications the KSB Calio family suits, and which information matters when selecting a pump.
The key difference: circulating versus pressurising
Circulator pump
A circulator pump moves the same water around a closed loop. Water enters the pump inlet, the rotating impeller accelerates it outwards, and this velocity is converted into pressure in the casing.
In a closed circuit the water columns in the flow and return lines balance each other. So even in a multi-storey building the circulator does not work against the building height; it only overcomes friction losses in pipes, valves and equipment. That is why circulators have a low head and low energy consumption.
Typical applications:
- Radiator and underfloor heating circuits
- The collector circuit of pumped (closed-circuit) solar systems
- Domestic hot water circulation lines (from the storage tank to the taps and back)
Booster pump (pressure boosting system)
A booster pump delivers water under pressure to the point of use in an open network. Its job is to make water flow with sufficient flow rate and pressure when a tap is opened. Here the pump must overcome both the building height and the required pressure at the tap.
Typical applications:
- Homes and buildings with insufficient mains pressure
- Distributing water from a storage tank through a building
You can find KSB Multi-Eco booster units, designed for single and two-family homes, on the product page.
| Circulator pump | Booster pump | |
|---|---|---|
| System type | Closed circuit | Open network |
| Task | Circulating water | Delivering water under pressure |
| Overcomes building height? | No, only the circuit losses | Yes |
| Increases tap pressure? | No | Yes |
KSB Calio pumps are not self-priming
The pumps in the KSB Calio family are non-self-priming circulators. In practice this means:
- The pump cannot draw water from a tank, well or container located below it. It cannot prime itself by sucking in air.
- There must always be water and a certain pressure at the pump inlet. The required minimum inlet pressure is given in the product's installation and operating manual and in the technical details on the product page.
- If the water level in the tank is above the pump, water flows to the pump by gravity and the pump can operate. If the level drops below the pump, it cannot deliver water.
- The pump must not run dry. In these pumps the bearings are lubricated and cooled by the pumped water. Running without water damages the bearings.
Which Calio pump can be used for domestic water?
For domestic water (water of drinking water quality), the pump materials must be approved for this use. In the KSB Calio family the situation is as follows:
| Model | Domestic and drinking water | Suitable application |
|---|---|---|
| Calio, Calio Pro, Calio Pro Plus (including twin models) | Not suitable | Heating, air-conditioning and closed-circuit systems (heating water, water and glycol mixture) |
| Calio SI, Calio SI HP, Calio SI HP MINI | Not suitable | Heating systems, pumped solar circuits |
| Calio SI Therm, Calio SI HP MINI Therm, CalioTherm Pro | Suitable | Drinking water applications, domestic hot water circulation |
These Therm models are also circulator pumps. Their correct place in a domestic water system is the circulation line, where hot water flows from the storage tank to the taps and back. This way hot water arrives without waiting when a tap is opened, and less water is wasted. Increasing the water pressure at the tap is not their job.
For water quality, temperature limits and other operating conditions, refer to the technical details on the product page and the manuals on the Product Documents page.
Common situations
"Hot water takes a long time to arrive at the tap."
The water standing in the pipe between the storage tank and the tap has cooled down, and it must run out before hot water arrives.
- If the system has a circulation (return) line back to the storage tank, or one can be added, Calio SI Therm can be considered.
- Systems with a combi boiler usually have no return line. In that case the suitability of the installation must be assessed first.
"The hot water pressure is low; the tap flow is weak."
This is a pressure problem, and a circulator pump will not solve it. Taps generally need 1.5 to 2 bar for adequate flow. This is provided by a booster pump (pressure boosting system).
"I want to take water from a tank and supply it to the house."
This is an open system and requires a booster pump. If the tank is lower than the pump, a non-self-priming circulator cannot draw the water anyway.
"I am looking for a pump for a solar system."
There may be two different needs here:
- Pumped (closed-circuit) solar system: if a water and glycol mixture circulates between the collector and the storage tank, Calio SI can be considered. It offers a PWM profile compatible with solar controllers (profile C), a constant pressure control mode and suitability for water and glycol mixtures.
- Boosting the pressure of water from a rooftop solar tank: common in detached houses, this is a pressure problem and is usually solved with a booster pump or pressure booster. Circulators are not designed for this purpose.
Information needed for pump selection
Whether a pump performs as expected depends on many factors such as pipe diameters, line lengths, height differences and pressure losses in valves and equipment. These are best determined by assessing the installation on site. Reviewing the following points with your installer or design engineer is the basis for the right choice:
- What problem needs solving? Hot water arriving late, low water pressure, distributing water from a tank, or circulating water in a closed circuit (heating, solar collector circuit, etc.).
- Where does the water come from? Combi boiler, storage tank, mains, tank or rooftop solar tank.
- Is the water source higher or lower than the planned pump location?
- Does the system have a return line?
- Line lengths, height differences and pipe diameters.
- Required flow rate and head (determined by system calculation).
Summary
- To circulate water in a closed circuit you need a circulator pump; to deliver it under pressure to the point of use you need a booster pump.
- KSB Calio pumps are not self-priming; there must always be water and sufficient pressure at the inlet.
- For domestic and drinking water, only the Therm models of the Calio family (Calio SI Therm, Calio SI HP MINI Therm and CalioTherm Pro) may be used.
- For pumped solar collector circuits, Calio SI can be considered.
- For the right choice, the installation should be assessed as a whole, preferably on site by a specialist.