The boiler can heat the water and the radiator can release the heat into the room. But without a pump moving the water in between, heat does not reach where it is needed fast enough in a modern system.

How does it work?

Water enters through the pump’s suction port and the rotating impeller accelerates it outwards. In the flow path of the casing this velocity turns into pressure and the water leaves through the discharge port (KSB manual).

In a closed circuit, the water columns in the flow and return lines balance each other. That is why, even in a ten-storey building, the pump does not work against the height of the building; it only overcomes the losses in the circuit.

This is the key difference from a booster pump. A booster pump delivers water under pressure to the point of use in an open network. A circulator pump circulates the same water in a closed loop.

Wet rotor versus dry rotor pumps

Most circulator pumps used in building services today are wet rotor pumps. In this design the rotor turns inside the pumped fluid, so no mechanical seal is needed.

PropertyWet rotorDry rotor
Rotor positionInside the fluidOutside the fluid, separate motor
Bearings and coolingBy the fluidRolling bearings and motor fan
Shaft sealNot requiredMechanical seal required
MaintenanceVery little; the KSB Calio series is specified as maintenance-freeSeal and bearings checked periodically
Typical useHomes, commercial buildings, circuits with small to medium flow ratesHigh-flow boiler rooms and process circuits

The circulator pumps in KSB’s Calio family are wet rotor pumps. The fluid both lubricates and cools the rotor assembly, while the windings are completely separated from the fluid.

Where is it used?

KSB lists the main applications for Calio Pro Plus as follows:

  • Single-pipe and two-pipe heating systems
  • Underfloor heating systems
  • Boiler or primary circuits
  • Hot water cylinder and storage tank circuits
  • Solar thermal systems and heat pumps
  • Ventilation, air-conditioning and cooling circuits

Domestic hot water recirculation is a separate matter. For applications in contact with drinking water, only models designed for it should be chosen. In the Calio SI manual, for example, KSB states that the heating model must not be used for drinking water and that the Calio SI Therm model should be chosen instead.

How do you read a pump name?

Catalogue names look confusing at first, but they usually describe the connection and the pump’s limits. Our Products page includes this reading guide too. The example from KSB’s manual, Calio SI 15-70-130, reads as follows:

  • 15: G 1 connection
  • 70: 7 metres of head (the value is written multiplied by 10)
  • 130: 130 mm overall length

There is an important detail here. The head in the name is the pump’s value at zero flow. So a “7-metre pump” will not circulate water at a 7-metre head in your system. The actual operating point is read from the flow-head curve.

The nameplate also shows the energy efficiency index (EEI), pressure rating (PN), temperature class (TF) and power range. These values are useful when selecting a pump and just as useful when replacing an old one.

Why has variable speed become standard?

Heating demand changes throughout the day. When thermostatic valves close, the system needs less flow. A fixed-speed pump does not follow this change and may draw more power than necessary.

A frequency-controlled, or variable speed, pump adjusts its speed to demand. As KSB reports, the EU phased out the placing on the market of fixed-speed circulators from 2013 onwards. In Türkiye, too, the EEI limit for standalone glandless circulators has been 0.23 since 1 February 2016.

According to KSB’s example for Germany, about a quarter of the circulators there are more than 20 years old, and half of these still run at a fixed speed. So in an older building, one of the first things to check is the age of the pump in the boiler room.

Key terms

The same few terms keep coming up when you read catalogues and compare quotes.

TermMeaningWhy it matters
Flow rate (Q)Fluid circulated per unit of time, m³/hDetermines the amount of heat transported
Head (H)The resistance the pump can overcome, in metres or mWCMust cover the losses in the circuit
Operating pointWhere the pump curve and system curve intersectShows the flow rate the pump will actually deliver
PNPressure ratingMust suit the maximum pressure of the system
TFTemperature classTF 110, for example, describes the limit for fluid temperature
EEIEnergy efficiency indexCompares pumps by the same rule

How can you tell if something is wrong with the pump?

The following symptoms point to a problem but do not prove that the pump is the cause:

  • Distant radiators stay cold or warm up late while the boiler is running.
  • The flow line is very hot and the return line much colder than expected.
  • There is a rushing or gravel-like noise from the pump.
  • An error code appears on the display.
  • The pump does not turn after a long standstill. KSB pumps have an unblocking function for this situation.

Rule out the simple causes first: electricity, a closed valve, system pressure, air and a clogged strainer. If none of these explains the problem, have the pump checked by an authorized service partner.

Three points matter for safety. According to the KSB manual, the pump must never run without fluid and the hot surface of a running pump must not be touched. When the pump is dismantled, people with pacemakers must keep at least 0.3 metres away because of the strong magnetic field around the rotor.

Frequently asked questions

Are a circulator pump and a circulating pump the same thing?

In everyday use, yes. Both describe a pump that moves fluid around a closed circuit.

Does a combi boiler have a circulator pump?

Most wall-hung combi boilers have the pump built in. Regulations treat such pumps as a separate “product-integrated” group. If the system grows, an additional external pump may be needed; plan this according to the boiler manufacturer’s connection diagram.

Is it normal for the pump to make noise when running?

Modern wet rotor circulator pumps are very quiet in normal operation. A distinct rushing or gravel-like noise usually points to air, low inlet pressure or a wrong setting. Our article on cavitation covers this in detail.

Next step

The next step in choosing the right pump is to determine the system’s flow and head requirements. Our pump selection guide explains these values step by step.