Installation
Where should a circulator pump be installed in the system?
When a new system is installed or an old pump is replaced, the most common question is: should the circulator pump go in the flow or the return line? The short answer is that this question alone does not decide it. The right position depends largely on where the expansion tank is connected to the circuit. To understand why, let us first take a brief look at how a closed heating circuit works.
The closed heating circuit in brief
A central heating system is a closed circuit filled with water. Its main components are:
- Boiler: heats the water.
- Flow line: carries the hot water from the boiler to the radiators.
- Radiators or underfloor heating: release the heat into the rooms.
- Return line: brings the cooled water back to the boiler.
- Circulator pump: moves the water around this loop. It does not lift the water; it only creates enough differential pressure to overcome the friction in the pipes and radiators.
- Expansion tank: water expands as it heats up; heated from 10 °C to 80 °C, its volume grows by about 3 percent. In a closed circuit this extra water has nowhere else to go. The expansion tank takes it up with its air cushion and keeps the system pressure within limits. Without the tank, the pressure would rise quickly and the safety valve would open.
The expansion tank has a second, less well-known role: the point where it is connected is where the pressure in the circuit is "anchored". That is why the first thing to check for the pump position is not the flow or return line but the tank connection. The general rule: the pump should come after the tank connection and pump away from the tank. If the boiler manufacturer's diagram requires a different layout, follow that diagram.
Why does the expansion tank determine the pump position?
In a closed circuit, a pump creates a pressure difference rather than pressure as such. At the point where the vessel is connected, the pump cannot change the pressure. The industry calls this the point of no pressure change. Of course the pressure changes here too as the water heats up, but that change is not caused by the pump.
So the difference created by the pump shows up in one of two ways:
- If it pumps away from the vessel: the difference appears as a pressure rise on the discharge side. Most of the system stays above static pressure.
- If it pumps towards the vessel: the difference appears as a pressure drop on the suction side. The pump inlet falls below static pressure.
As an example, consider a simple circuit with 1.5 bar static pressure at the vessel and a pump creating a 0.4 bar difference. We ignore building height and other effects.
| Layout | Pump inlet | Pump outlet |
|---|---|---|
| Pumping away from the vessel | approx. 1.5 bar | approx. 1.9 bar |
| Pumping towards the vessel | approx. 1.1 bar | approx. 1.5 bar |
The pump and vessel stayed the same; only the layout changed. In the second case the inlet pressure is 0.4 bar lower.
What does the wrong position do?
When pressure drops, air dissolved in the water comes out of solution, and air is the enemy of quiet flow. In tall buildings, with low fill pressure and automatic air vents at the high points, things get worse: where the pressure falls below atmospheric, these vents may start drawing air in instead of releasing it.
The usual consequences are:
- Flow noise in radiators and pipes
- Radiators that stay cold on upper floors
- Constant need for venting
- Risk of cavitation due to low inlet pressure
Many older systems may have run for years without trouble with the pump in the return line pumping towards the tank. This is often because older pumps created only a small differential pressure. With a pump that can create a higher differential pressure, the same layout may cause more problems. So do not assume the new pump will be trouble-free just because the old one was.
Flow or return?
Once the vessel rule is met, neither flow nor return is right or wrong in itself. The decision depends on several conditions.
| Situation | What to watch out for |
|---|---|
| Single-pump radiator circuit | The vessel connection should be on the pump’s suction side |
| High-efficiency boiler | The manufacturer may require the pump to push towards the boiler. In that case the tank connection is moved to the pump inlet |
| Multi-zone pumps | The tank connection should be on the suction side of the pumps. Problems may occur if one pump pumps away from the tank and another towards it |
| Primary-secondary circuit | Assess the circuits and vessel connection together; this design should be done by the system designer |
| Rooftop boiler room | There is little water column above the pump. Check the minimum inlet pressure separately |
Temperature also plays a part. A pump in the hot flow line may need a higher inlet pressure. So read the chosen model’s minimum pressure table at the actual line temperature. Details in our cavitation article.
How should the pump be installed?
How the pump is installed matters as much as where. The rules below are based on KSB installation and operating manuals. Also check the permitted installation positions in your model's manual; the manuals are on the Product Documents page, and installation position drawings are in the Technical details section of the product pages.
- Keep the shaft horizontal. The electronics box must never face downwards. If necessary, rotate the box, not the pipe.
- In a vertical pipe, flow should be upwards. With downward flow, fit an air vent at the highest point of the suction line.
- Avoid the lowest point. If the pump is placed at the lowest point of the system, dirt can collect in it.
- Follow the flow arrow. The arrow on the casing and insulation shell shows the direction of flow.
- Add valves. Shut-off valves are recommended on both sides of the pump. Leaks must not drip onto the pump.
- Do not load the pump with pipe weight. Support the pipe close to the pump and connect it without stress.
- Flush first. Clean the dirt out of the system before first start-up or replacement.
- Do not throttle the suction side. To prevent cavitation damage, do not throttle the flow on the suction side.
- Keep the pipe diameter. The pipe diameter should not be smaller than the pump’s port diameter.
- Check the surroundings. Ambient temperatures below zero are not permitted. For outdoor installation, protect the pump with a roof.
In cooling and chilled water circuits, condensation can form in the motor and electronics housing when the fluid is colder than the ambient air. For these applications, always check the conditions in the model's installation and operating manual.
Where do the strainer and air separator go?
A dirt separator is usually installed in the return line, before the boiler and the pump. This protects the pump, but when the filter clogs it also lowers the suction pressure. The filter therefore needs easy access and regular cleaning. For glycol systems, see also our glycol article.
The air separator is usually placed near the boiler outlet where the water is hottest, because air separates from water more easily there. Decide the final position together with the boiler manufacturer’s diagram and the project’s pressure distribution.
Example: replacing a pump in an older building
In a fictitious building, the old pump sits in the return line, pumping towards the vessel. The system has had venting problems for years. If a new, more powerful pump is installed in the same place, the problem may get worse. Before the replacement, these options are considered:
- Move the vessel connection: the pump stays where it is and the vessel is connected to the pump’s suction side.
- Move the pump: the pump is moved to a point after the vessel connection.
- Review the pressure: if changing the pipework is not possible, calculate whether the static pressure is sufficient within the limits of the safety valve and vessel.
Which option suits depends on the boiler diagram, the space available and the building height. The third option does not fix the root cause; it can only reduce the effect.
Quick check after installation
- The vessel connection is on the pump’s suction side.
- The pump does not conflict with the boiler manufacturer’s diagram.
- The shaft is horizontal and the electronics box correctly positioned.
- The flow arrow points the right way.
- The pump can be isolated with valves on both sides.
- The inlet pressure when hot is above the table value.
- Venting is complete.
Frequently asked questions
What happens if the pump is installed in the return line?
If the vessel connection is at the pump inlet, the return line can be fine. The problem is not the return line itself but the pump pumping towards the vessel.
Can I install the pump in a vertical pipe?
On most models yes, as long as the shaft stays horizontal. Flow should be upwards, or a vent should be added for downward flow. Check the permitted installation positions for your model.
Is it right to put the new pump where the old one was?
First check the vessel connection. If the old system has recurring air or noise problems, the replacement is a good opportunity to correct this mistake.